soon
Social Links
 

BCX Rectifier - 150

Power Systems

INOVAX is a partner of NEOPATH that develops, produces and diversifies its operations in the energy market for Telecommunications, with Rectifier Units (UR) and Rectifier Systems (SR) of 50 wa 2500 w. BCX and UR rectifiers were developed to provide faultless and high quality power supply, developing solutions and adaptations for new products.

BCX Rectifier - 150

The BCX – 150 Rectifier was developed to provide faultless and high quality power supply. Its high frequency switching technology allows the device to have reduced weight and size and to meet the highest requirements applicable to telecommunications equipment.

Technical Characteristics

Dimensions (in mm): 433 x 88 x 320 (W x H x D).

Mounting option: Cabinet, table, wall or rack 19” – 2U.

Rectifier Weight: 5 kg.

Battery module weight: 15 kg

Supply Voltage: 127/220 Vac ± 15% with external switch of choice 127/220 Vac (Preset to 127 Vac).

Rated voltage for consumer: -48 Vdc ranging from -42 Vdc (End of battery discharge) to -54.5 Vdc (Full charge of batteries).

Switching Frequency: 50 kHz.

Efficiency: > 80%.

Network Frequency: 50/60 Hz ± 5%.

Output Ripple: < 300m Vpp.

Maximum current for consumer: 5 a.

Drums: 4 times (12 V – 7 Ah).

Battery Charge: Automatic.

Operating Temperature: 0°C to 50°C.

Color code: Beige ED303B – Coutherland.

Front panel

LED Indicators:

B.C
Indicates when the mains input is outside the operating range of the Rectifier.
Temperature
Indicates when the internal temperature is above the operating limit of the Rectifier.
Output Voltage
Indicates whether the output voltage is normal.
DrumsIndicates whether the battery is charging or floating.
Puller
Assists in handling, insertion and removal of the battery drawer.
fuses
BAT, CONS.1, CONS.2, CONS.3.
Posts
Monitor the output voltage.
Rear panel

AC switch
Facilitates access to turn the equipment on and off

AC1 and AC2 Fuses Alarms - RELAY Dry Contact

Vac failure
Enabled: pin 2 of the DB-9 connector grounded;
Lack of Vac at the source input;
Abnormal Vac Voltage (Over or Under Voltage).
Low Voltage Battery
Enabled: pin 3 of the DB-9 connector grounded;
Low battery voltage near disconnect.

Mate-N-Lok 9-Pin Connector (optional)

PIN

OCCUPATION

1

+ CONSUMPTION

2

ALARM - LOW VOLTAGE BATTERY

3

ALARM - Vac FAILURE

4

COMMON / EARTH ALARM

5

– CONSUMPTION

6

SHIELDING

7

NOT USED

8

NOT USED

9

COMMON / EARTH

DB-9 9 Pin Connector (Alarm)

PIN

OCCUPATION

1

COMMON / EARTH ALARM

2

ALARM - Vac FAILURE

3

ALARM - LOW VOLTAGE BATTERY

Bendal Pin Bar Connector (Consumer)

PIN

OCCUPATION

PIN

OCCUPATION

1

+ CONS. 1

4

– CONS. two

2

– CONS. 1

5

+ CONS. 3

3

+ CONS. two

6

– CONS. 3

AC connector: 2P+T socket

Rear panel

AC switch
Facilitates access to turn the equipment on and off

AC1 and AC2 Fuses Alarms - RELAY Dry Contact

Vac failure
Enabled: pin 2 of the DB-9 connector grounded;
Lack of Vac at the source input;
Abnormal Vac Voltage (Over or Under Voltage).
Low Voltage Battery
Enabled: pin 3 of the DB-9 connector grounded;
Low battery voltage near disconnect.

Mate-N-Lok 9-Pin Connector (optional)

PIN

OCCUPATION

1

+ CONSUMPTION

2

ALARM - LOW VOLTAGE BATTERY

3

ALARM - Vac FAILURE

4

COMMON / EARTH ALARM

5

– CONSUMPTION

6

SHIELDING

7

NOT USED

8

NOT USED

9

COMMON / EARTH

DB-9 9 Pin Connector (Alarm)

PIN

OCCUPATION

1

COMMON / EARTH ALARM

2

ALARM - Vac FAILURE

3

ALARM - LOW VOLTAGE BATTERY

Bendal Pin Bar Connector (Consumer)

PIN

OCCUPATION

PIN

OCCUPATION

1

+ CONS. 1

4

– CONS. two

2

– CONS. 1

5

+ CONS. 3

3

+ CONS. two

6

– CONS. 3

AC connector: 2P+T socket

Protection

External fuses: AC1, AC2, BAT, CONS. 1, CONS. 2, CONS. 3.

Temperature Limiter: In the power stage.

Undervoltage Circuit: At the entrance to the mains.

Overvoltage Circuit: At the consumer's exit and at the entrance to the electrical network.

Overload Circuit and Short Circuit: At the consumer's exit.

Automatic battery disconnection at maximum discharge limit (-42 Vdc).