soon
Social Links
 

UR Rectifier - 1048

Power Systems

INOVAX is a partner of NEOPATH that develops, produces and diversifies its operations in the energy market for Telecommunications, with Rectifier Units (UR) and Rectifier Systems (SR) of 50 wa 2500 w. BCX and UR rectifiers were developed to provide faultless and high quality power supply, developing solutions and adaptations for new products.

UR Rectifier - 1048

The UR – 1048 Rectifier was developed to provide continuous power for telecommunications systems or equipment that operate in the range of 42Vdc to 55Vdc.

This 48 Vdc DC Power Supply Rectifier, UR1048-D, was designed to work in parallel with another rectifier, in a redundant manner, so that, in the event of a failure of one of the rectifiers, the other continues to operate and supply the consumer . The UR1048-D powers the consumers and keeps the battery charged or floating so that any failure in the electrical network does not leave the consumers unpowered.

Although it can be applied in several “niches”, this rectifier was developed to supply equipment in the telecommunications area.

Technical Characteristics

Dimensions (in mm): 245 x 82 x 273 (W x H x P ).

Mounting option: 19” Rack – 2U, Table, Wall or Tray.

Rectifier Weight: 5 kg.

Supply Voltage: 127/220 Vac ± 15% with internal switch of choice 127/220 Vac (Pre-configured for 127 Vac).

Rated voltage for consumer:

UR-1048D: -48 Vdc with variation between –42 Vdc (End of battery discharge) to –54.5 Vdc (Full charge of the batteries);

UR-1224D: +24 Vdc ranging from +22 Vdc (End of battery discharge) to +27.4 Vdc (Full battery charge).

Switching Frequency: 50 kHz.

Efficiency: 80%.

Network Frequency: 50/60 Hz.

Output Ripple:

UR-1048D: <300m Vpp;

UR-1224D: < 200m Vpp.

Maximum current for consumer:

UR-1048D: 10A; UR-1224D: 12A.

DFC: Parallelism with Forced Current Division.

Fast Battery Charge: Manual or automatic.

Operating Temperature: 0°C to 50°C.

Float voltage adjustment and battery bank charge.

Consumer current limiting adjustment.

Connection Capacity: Without battery: up to 4 Rectifiers without Supervision Unit.
With battery: 5 to 6 Rectifiers with Supervision Unit.

Color code: Beige ED303B – Coutherland.

Front panel

LED Indicators:

B.C
Indicates when the mains input is outside the operating range of the Rectifier.
Temperature
Indicates when the internal temperature is above the operating limit of the Rectifier.
Output Voltage
Indicates whether the output voltage is normal.
Drums
Indicates whether the battery is charging or floating.
AC switch
Provides access to turn the Rectifier on and off.
Puller
Assists handling, insertion and removal of the Rectifier.
Posts
Monitors output voltage.
Rear panel

Alarms - RELAY Dry Contact

Vac failure Enabled: short from pin 1 to pin 2 of connector
DB-9;
Lack of Vac at the source input;
Abnormal Vac Voltage (Over or Under Voltage).

Low Voltage Battery Enabled: short from pin 3 to pin 4 of connector
DB-9;
Low battery voltage near disconnect.

BLZ Plug-in Connector (Network)

PIN

OCCUPATION

1

EARTH

2

NEUTRAL

3

PHASE

BLZ Plug-in Connector (Consumer)

PIN

OCCUPATION

PIN

OCCUPATION

1

– BAT

4

– CONS.

2

+ BAT

5

VAGUE

3

+ CONS.

6

EQUALIZATION

DB-9 9 Pin Connector (Alarm)

PIN

OCCUPATION

1

ALARM - Vac FAILURE

2

ALARM - Vac FAILURE

3

ALARM - LOW VOLTAGE BATTERY

4

ALARM - LOW VOLTAGE BATTERY

Protection

Internal fuses: AC1, AC2, BAT, CONS.

Temperature Limiter: In the power stage.

Undervoltage Circuit: At the entrance to the mains.

Overvoltage Circuit: At the consumer's exit and at the entrance to the electrical network.

Overload Circuit or Short Circuit: At the consumer's exit.

Automatic battery disconnection at maximum discharge limit: (-42 Vdc / UR-1048D) and (+22 Vdc / UR-1224D).