BCX Rectifier - 300
INOVAX is a partner of NEOPATH that develops, produces and diversifies its operations in the energy market for Telecommunications, with Rectifier Units (UR) and Rectifier Systems (SR) of 50 wa 2500 w. BCX and UR rectifiers were developed to provide faultless and high quality power supply, developing solutions and adaptations for new products.

BCX Rectifier - 300
The BCX300 power supply is a voltage rectifier that provides continuous power for telecommunication systems or equipment operating in the -43Vdc to -55Vdc range.
This rectifier is composed of two modules: the first module consists of a switched source with battery charger and the second, of a bank of sealed batteries with an autonomy of approximately 4 hours. The two modules are fixed in a sub-rack for installation in a standard 19” RACK.
The BCX300 supplies power points and keeps the battery charged or floating so that any mains failure does not leave consumers without power. This source is ideal for powering equipment in the telecommunications area.
Technical Characteristics
Dimensions (in mm): 483 x 266 x 334mm (W x H x D).
Rectifier Weight: 30kg
Supply Voltage: 127/220Vac ± 15% with external switch of choice 127/220Vac (pre-configured for 127Vac).
Rated voltage for consumer: -48Vdc with a variation range from -43Vdc (discharge end) to 55Vdc (load end).
Total capacity: 5 a.
Power Voltage Frequency: 50/60 Hz ± 5%.
Switching Frequency: 50KHz.
Ripple: < 480mV.
Static Voltage Regulation: ± 1% for grid and load variation from 5% to 200% Inominal.
Static Current Regulation: < 5% Inominal.
Dynamic Voltage and Current Regulation: < 10mS
Drums: 4x (12V-18Ah).
Performance: > 80%.
Battery Bank Autonomy: 4 hours.
Color code: Beige ED303B – Coutherland.
Front panel
Front Panel Elements
3 and ½ digit LCD digital meter for voltage or current measurement.
Voltage or current selector switch for display.
Vac voltage LED (BICOLOR) – AC.
Temperature LED (BICOLOR) – TEMPERATURE.
Output voltage LED (BICOLOR) – OUTPUT VOLTAGE.
Battery LED (BICOLOR) – BATTERY.
On/Off Switch – AC.
Mains fuses (AC1 and AC2), battery (BAT.) and consumer (CONS.1, CONS.2 and CONS.3).
Glass fuse delayed action 6Ax250V – 20AG (5x20mm) – AC1, AC2, BAT., CONS.
LED function:
- LED 1 - AC
– Off: lack of Vac voltage – Power off, Battery discharged.
– Green: Normal Vac voltage – Power on, Battery charging or floating.
– Red: Abnormal Vac voltage (Over or Under Voltage) – Power off, Battery discharged.
LED 2 - Temperature
– Green: normal temperature.
– Red: abnormal temperature – Power off, Battery discharging.
LED 3 - Consumer Voltage
– Off: lack of voltage for Consumer.
– Green: Voltage for normal Consumer.
– Red: Normal Consumer voltage – Low Battery Voltage close to Disconnect.
LED 4 - Battery
– Green: normal voltage.
– Red: Low voltage – Battery charging or Battery discharged.
Rear panel
AC switch
Facilitates access to turn the equipment on and off
AC1 and AC2 Fuses Alarms - RELAY Dry Contact
- Vac failure
- Enabled: pin 2 of the DB-9 connector grounded;
Lack of Vac at the source input;
Abnormal Vac Voltage (Over or Under Voltage). - Low Voltage Battery
- Enabled: pin 3 of the DB-9 connector grounded;
Low battery voltage near disconnect.
Mate-N-Lok 9-Pin Connector (optional)
|
PIN |
OCCUPATION |
|
1 |
+ CONSUMPTION |
|
2 |
ALARM - LOW VOLTAGE BATTERY |
|
3 |
ALARM - Vac FAILURE |
|
4 |
COMMON / EARTH ALARM |
|
5 |
– CONSUMPTION |
|
6 |
SHIELDING |
|
7 |
NOT USED |
|
8 |
NOT USED |
|
9 |
COMMON / EARTH |
DB-9 9 Pin Connector (Alarm)
|
PIN |
OCCUPATION |
|
1 |
COMMON / EARTH ALARM |
|
2 |
ALARM - Vac FAILURE |
|
3 |
ALARM - LOW VOLTAGE BATTERY |
Bendal Pin Bar Connector (Consumer)
|
PIN |
OCCUPATION |
PIN |
OCCUPATION |
|
1 |
+ CONS. 1 |
4 |
– CONS. two |
|
2 |
– CONS. 1 |
5 |
+ CONS. 3 |
|
3 |
+ CONS. two |
6 |
– CONS. 3 |
AC connector: 2P+T socket
Protection
Fuses on each phase and on the -CONS outputs. and -BAT.
Output overload/short circuit through current limiting.
Varistor at the mains input.
Automatic shutdown for high mains and low mains.
High and Low Voltage Sensor on the Consumer.
High Temperature Sensor.
Automatic Battery Disconnect Device.
Automatic Battery Bank Recharge.
Remote signaling and local abnormality common of the following events: AC failure, internal fault and service switch off, voltage high and voltage low.
Remote Signaling and Local Low Battery Voltage near disconnect.